Venture Lighting International: Bright Ideas, Bold Innovations
An Advanced Lighting Technologies Company Lamps by Venture Ballasts

Techincal Information
Search by product

Venture Contact Info

PROBLEM 1 LAMP WILL NOT START
PROBLEM 2 LAMP LIFE IS REDUCED
PROBLEM 3 LAMP FLICKERS OR CYCLES ON AND OFF
PROBLEM 4 LAMP STARTS SLOWLY (ARC DOES NOT STRIKE WHEN 
SWITCH IS TURNED ON.)
PROBLEM 5 FUSES BLOW OR CIRCUIT BREAKERS OPEN ON LAMP START UP
PROBLEM 6 LAMP LIGHT OUTPUT LOW
PROBLEM 7 ARC TUBE BECOMES BLACKENED OR SWOLLEN EARLY IN LIFE OR LAMP/ARC TUBE MAY SHOW SIGNS OF SCORCHING
PROBLEM 8 DIFFERENCE IN LAMP COLORS POSSIBLE CAUSE CORRECTIVE ACTION

PROBLEM 1— LAMP WILL NOT START

POSSIBLE CAUSE

CORRECTIVE ACTION

1. No Power to Ballast

Check fuses or other causes of power outages.

2. Normal End of Lamp Life

Often the simplest procedure is to test the lamp in an adjacent fixture which is known to be operating properly and then replace as necessary. It should be kept in mind that series ballasts will occasionally extinguish the adjacent lamp if one is removed.

3. Lamp Loose in Socket

Inspect the lamp to see if there is any indication of arcing at center contact button. Tighten lamp to seat it properly. If base is distorted and will not seat properly in the socket, replace lamp.

4. Optical & Other Sensing Devices Inoperative

Replace sensing device. (Check this by covering sensing device to block out light while power is applied to fixture.)

5. Defective or Improper Wiring

Examine wiring to ensure it conforms with wiring diagram on the ballast label. Check primary wiring to ballast and from ballast to socket to establish circuit continuity. Check connections to see that they are secure. Check for under-sizing of wire gauge, resulting in lowered voltage. Repair circuit.

6. Voltage at Fixture Too Low

Measure line voltage at input of ballast. For most types of ballasts, measured line voltage should be within 10% of label rating. With many types of distribution systems, increased loading or demand decreases available voltage at the ballast primary. Therefore, ideally, a check should be made at full load. If tapped ballast, match ballast tap connection to supply voltage measured at ballast. Increase supply voltage if feasible. Verify that lamp to remote ballast distance is acceptable.

7. Incompatible Ballasting

Correct ballasting is essential for dependable HID lamp operation. Any HID lamp will perform erratically or fail to start on an incorrect ballast. Make sure that the ballast label data agrees with the line voltage and lamp used. Incorrect ballasting will generally cause a lamp to fail prematurely.

8. Defective Shorted Ballast

A shorted ballast will generally cause the seals at the end of the arc tube to rupture with an indicative blackening in the seal ring area. Shorted condition may be due to shorted capacitors, shorted leads or shorted winding. Replace components as required.

9. Improper Lamp Operating Position (Metal Halide Only)

The operating position should agree with the lamp specifications. A BU-HOR lamp can be operated base up, vertical to, and including the horizontal, and BD can be operated base down, vertical to, approaching, but not including the horizontal. A lamp operated beyond the specified position may not start and degrade lamp performance if it does start. 

10. Lamp Has Been Operating : Cool Down Time Insufficient (Hot Restrike)

When HID lamps are operating and the supply voltage is cut or interrupted, the lamps will require a period of time to cool and re-establish optimum starting conditions. Bare mercury and metal halide lamps require from four to eight minutes cool down time. High pressure sodium lamps require approximately one minute to cool before restriking. In a luminaire, restart time varies with the degree of ventilation built into it, ambient temperature, and draft conditions. The time from cool to restartable condition can realistically range up to 20 minutes for mercury and metal halide lamps in tight luminaires.

11. High Restrike Voltage (Metal Halide Only)

This condition is peculiar to the metal halide lamp. It does not occur with mercury. If the supply voltage to a metal halide lamp is interrupted during the warm up period, the subsequent restrike voltage (voltage required to restart the lamp) may be higher than that required for a lamp which has been allowed to stabilize (come up to full output normally) or to cool down to normal room temperature.
12. Improper Ballast for Lamp Operating Conditions Environmental conditions such as extreme temperatures, high humidity and other factors affect ballast operation. Check lamp environmental operating conditions against published performance.
13. End of Ballast Life The appearance or condition of a ballast may give a clue to whether it is good or not. If it is charred, it may have been subjected to sustained excessive heat. Swollen capacitors indicate trouble. Check with appropriate testers, ammeter, and voltmeter. Frequently, the failure mode of a ballast is capacitor failure with consequent low power factor operation and high current. This leads to overheating of the core and coil and eventual failure.
14. Defective Ignitor

Insure that the lamp is good. Disconnect the ignitor and install a specified test lamp. If the test lamp lights, the ballast is good but the ignitor is not. Replace ignitor. If the test lamp does not light, the ballast has most likely reached its end of life.

15. Mismatched Ignitor Verify that the ballast and ignitor are matched according to the specifications. Replace if necessary.
16. Lamp Defects

Common defects that require the lamp to be replaced include:

  • Arc tube leak
  • Open welds
  • Probe or cathode moly electrolysis
  • Diode or switch shorted
  • Quartz devitrification around rod
  • Sodium leak
  • Open diode

Back to top

PROBLEM 2—LAMP LIFE IS REDUCED

POSSIBLE CAUSE

CORRECTIVE ACTION

1. Lamp Physically Damaged

Investigate the possibility of outer bulb damage from handling or transportation that may have cracked glass. If air enters outer bulb, arc tube may continue to burn for 100 hours before failure. Check to see if the bulb is broken where glass meets the base due to twisting lamp too firmly into socket or scoring of glass where socket inadvertently touches the lamp bulb. Look for broken arc tube or loose metal parts. A leak in the outer bulb will cause oxidation of the metal parts inside. In high pressure sodium, the dark gettering material in the neck of the bulb near the base will turn white or disappear. Replace lamp.

2. Wrong Ballast

Make sure that the ballast label agrees with the line voltage and the installed lamp. The 1,000 watt Mercury lamp, for example, is made in the H34 (High Current) and the H36 (Low Current) types with a separate ballast available for each type. If the H34 ballast is used with the H36 lamp or vice versa, the life of the lamp will be adversely affected and can destroy the ballast. A similar situation exists with S55, S56 and S63 150 watt high pressure sodium lamps. 

3. Lamp Operating in Incorrect Position

Either change positioning of fixture or replace lamp with one suitable for that position.

4. Faulty Capacitor

To check capacitor, disconnect and discharge it. Then, using an ohmmeter, set to the highest scale, check for faults, 1) if meter reads low resistance initially and increases, capacitor is good. 2) if meter reads low resistance initially and remains the same, the capacitor is SHORTED and should be replaced. 3) if meter reads high resistance initially and remains the same, the capacitor is OPEN and should be replaced.

Back to top

PROBLEM 3— LAMP FLICKERS OR CYCLES ON AND OFF

POSSIBLE CAUSE

CORRECTIVE ACTION

1. Wrong Ballast

With mercury lamps, improper ballasting can cause flickering or erratic operation. With metal halide lamps, the effect is generally noticed in the startup period when the lamp ignites, starts to warm up and then extinguishes (cycling). This may be caused by improper voltage/current relationships delivered by ballast. Under certain conditions new lamps may "cycle". Usually after three tries to start at 30 to 60 second intervals lamps will stabilize and operate normally.

2. High Lamp Operating Voltage/Low Open Circuit Ballast Voltage

Measure lamp operating voltage. Measure ballast open circuit voltage. Replace as required.

3. Variable Voltage

Heavy motor loads or welding appliances on line can cause flickering during operation. Remove lighting circuits from the circuits serving these devices. Provide voltage regulators. Check for loose connection. Use of Constant Wattage Isolated (CWI) ballasts not Constant Wattage Auto (CWA) can frequently help this situation.

4. HPS Cycler

As a high pressure sodium lamp is burned for long periods of time, its operating voltage tends to increase. When this point is reached, the lamp will exhibit cycling on and off characteristics. This is normal end of life lamp. Replace the lamp after checking ballast open circuit voltage and lamp operating voltage.

Back to top

PROBLEM 4—LAMP STARTS SLOWLY (ARC DOES NOT STRIKE WHEN SWITCH IS TURNED ON.)

POSSIBLE CAUSE

CORRECTIVE ACTION

1. Hard Starter A hard starter is a lamp which will not start rapidly. It may glow for extended periods of time destroying cathodes. It should be replaced after checking voltage and ballast.

PROBLEM 5— FUSES BLOW OR CIRCUIT BREAKERS OPEN ON LAMP START UP

POSSIBLE CAUSE

CORRECTIVE ACTION

1. Overloaded Circuit

Rewire to accommodate starting current of lamp/ballast combination.

2. High Momentary Transient Current

Can be caused by reactor or autotransformer ballasts which draw high initial currents. Use current protective devices incorporating time delay elements. If these fail, change ballast as its characteristics will affect lamp life.

PROBLEM 6—LAMP LIGHT OUTPUT LOW

POSSIBLE CAUSE

CORRECTIVE ACTION

1. Normal Light Output DepreciationThroughout Life

 

Refer to maintenance characteristics of lamp in technical publications comparing light output vs. burning time. If depreciation is within published range, replace lamp.

2. Incorrect Voltage

Check ballast label to see if rating designation conforms to lamp rating description. Correct if necessary. Check line voltage at ballast and set ballast tap to voltage reading. If not tapped, check ballast voltage range against input voltage. Check wiring connections for voltage loss points. Check socket contact point. Use CWI ballast.

3. Incorrect Ballast Output

Check ballast output to determine if it conforms to lamp requirements. If voltage and current do not stabilize in five to ten minutes warm-up time, ballast output is incorrect and adjustment should be made. Check capacitor wiring, if visibly available, to determine if capacitors are properly wired.

4. Dirt Accumulation

Check and clean lamp and luminaire. Establish maintenance program.

5. Faulty Capacitor

Check capacitor rating to specification. Measure capacitance to specification using capacitance meter. Replace capacitor if necessary.

Back to top


PROBLEM 7—ARC TUBE BECOMES BLACKENED OR SWOLLEN EARLY IN LIFE

LAMP/ARC TUBE MAY SHOW SIGNS OF SCORCHING

POSSIBLE CAUSE

CORRECTIVE ACTION

1. Overwattage Operation Improper Ballasting

Check for possibility that lamp is operated on ballast designed for higher wattage lamp. Overwattage operation can cause premature blackening. Check ballast label against lamp specification.

2. Excessive Current or Shorted Capacitor(s)

Check voltage at ballast. Check for possibility of current or voltage surges which can damage arc Voltage tube or seals or burn up connecting ribbons inside outer tube. Check for shorted capacitors and replace ballast if shorts are found.

3. Reflector Problem

Reflector design may refocus radiant energy directly on the arc tube or other parts of the lamp causing overheating. Limits for allowable voltage rise due to fixture effect are listed in High Pressure Sodium Engineering Bulletins. If this is suspected, the luminaire should be tested in a laboratory.

4. "Glow State" Operation

Under certain lamp and/or ballast operating conditions, lamps will go into a partial discharge (dim glow) which will darken arc tube and cause short life. Replace lamp and check ballast.

Back to top

PROBLEM 8—DIFFERENCE IN LAMP COLORS

POSSIBLE CAUSE

CORRECTIVE ACTION

1. Normal Maintenance

In addition to the normal decrease in light output or brightness, a color shift can occur as lamps age. Spot replacement of failures with new lamps may show very noticeable differences in lamp colors. A group relamping program minimizes this problem.

2. Wrong Lamp Color

Check etch on lamps which appear different to see that they are actually the same color. Replace with correct color lamp.

3. Range of Manufacturing Tolerances

Due to tolerance ranges from manufacturers, slight differences in color can be corrected by grouping those of similar color.

4. Variations in Luminaires

Variations in the surface or finish of the reflectors and/or lenses can introduce color differences. Interchange lamps to check on possible luminaire differences. Dirty fixtures can also create differences, emphasizing the importance of adequate maintenance.

5. Variations in the Environment

In common with luminaire variations, color differences in ceilings, walls, floors and furnishings as well as other sources of illumination in the area can affect the appearance of the lamp color.

6. Faulty Capacitor

Check capacitor rating to specification. Measure capacitance to specification, using capacitance meter. Replace capacitor if necessary.

 
li li
   © 2019 Venture Lighting International, Inc. | Privacy